The LFT3080 anti-corrosion liquid level transmitter uses an anti-corrosion ceramic flat diaphragm pressure core as the measuring element, the shell is made of corrosion-resistant plastic material, and the air guide cable is made of special anti-corrosion liquid level wire made of PTFE material. This anti-corrosion submersible liquid level transmitter is mainly used for liquid level measurement of corrosive media such as acids and alkalis. The product has been reliably sealed at the joints of each key link such as the shell and the wire, ensuring that the product has good sealing performance. It is widely used in many fields such as chemical industry, environmental protection, medicine, and industrial process control.
* Adopts high-precision and high-overload ceramic flat diaphragm core
* Excellent corrosion resistance
* Removable bottom anti-blocking cap, prevent accidental damage to the diaphragm, facilitate regular cleaning
* Shell adopts a multi-protection and sealing structure design
Transmitter
| Measuring Range | 0~1…200mH₂O | ||
| Overload Pressure | 1.5 times the rated pressure | ||
| Accuracy ① | ±0.5%F.S、② ±1%F.S ③ | ||
| Stability | <0.5%F.S/year | ||
| Working Temperature | -10~70℃ | ||
| Storage Temperature | -10~70℃ | ||
| Measured Medium | Liquid compatible with 1Cr18Ni9Ti, polytetrafluoroethylene (PTFE), fluorine rubber (FKM), full gas ether rubber (FFKM) | ||
| Electrical Properties | 2 wired | 3 wired | 4 wired |
| Output Signal | 4~20mA | 0~10V | RS485 |
| power Supply | 10~36VDC | 15~36VDC | 10~36VDC |
| Electrical Connection | Direct outlet | ||
| Pressure Port | Submersible/M20*1.5 installation type | ||
| Housing Protection Level | IP68 | ||
| Pressure Form | Gauge pressure G | ||
①: Measured at 25℃, including the comprehensive accuracy of linearity, repeatability and hysteresis;
②: When the range is greater than 2mH₂O, the accuracy is ±0.5%F.S;
③: When the range is less than or equal to 2mH20, the accuracy is ±1%F.S
Size Chart (unit:mm)


Adopts high-precision and high-overload ceramic flat diaphragm core
Excellent corrosion resistance
Removable bottom anti-blocking cap, prevent accidental damage to the diaphragm, facilitate regular cleaning
Shell adopts a multi-protection and sealing structure design
Applicable Fields:
Chemical industry
Environmental protection
Medicine
Industrial process control
Product Inquiry
03 Aug 2026
Engineering Factors That Shape Water Filter Booster Pump Performance in RO Systems01 Aug 2026
Optimizing Booster Pump Performance for Different RO Water Purification Systems30 Jul 2026
Enhancing RO Water Output Efficiency With Advanced Booster Pump Technology28 Jul 2026
Solving Viscous and Corrosive Fluid Handling Challenges With Stepper Peristaltic Pumps
English
français
Deutsch
Español
italiano
русский
português
العربية
Türkçe
Zulu 