Email Us

Lefoo Wall Mounted CO2 Monitor Transmitter LFG201 (Upgraded Ver.)

LEFOO LFG201 wall-mounted carbon dioxide transmitter (Upgraded Ver.) is based on the fact that different gases have different absorption capabilities for infrared light in a specific band. It measures the concentration of the measured gas by measuring the degree of infrared light absorption. Compared with electrochemical sensors, it has the characteristics of long life, good stability, wide power supply range and power supply anti-reverse connection protection. It is suitable for carbon dioxide gas measurement in indoor air quality detection, air conditioners, air purifiers, vegetable greenhouses and other occasions.

* Update PointThe core has been upgraded, solving the stability failure issues of the original core during the production process and at the customer end, making it more durable and more secure. Except for the rear wiring method, all other parameters can still be achieved.


Features

* Imported infrared light source and dual-channel thermopile detector

* The sensor is oxygen-free and has a service life of more than 5 years

* Long-term stability and reliability

* Double-layer waterproof membrane design effectively prevents water vapor from entering

Specification of Wall Mounted CO2 Monitor Transmitter LFG201 (Upgraded Ver.)

Technical parameter

LEFOO Wall Mounted CO2 monitor transmitter LFG201 (Upgraded Ver.)
Output4-20mA(3-wire)0-5V(3-wire)0-10V(3-wire)RS485(4-wire)
Working Voltage10-30VDC10-30VDC16-30VCD10-30VDC
Working Temperature-10℃~50℃
Working Humidity0-80%RH(no condensation)
Measure Concentration0-2000PPM/0-5000PPM/0-10000PPM
Accuracy±(40PPm+ 3%Fs)@25
Preheat Time2min(available)-10min(maximum accuracy)
Protection ClassIP65
Service Life>5years



Dimension

201size.jpg

Wiring Guide


RS485 digital output wiring guide
Power supplyRedPower positive 
BlackPower negative
CommunicationGreen485-A
White485-B


Voltage/current analog output wiring guide
Power supplyRedPower positive 
BlackPower negative
CommunicationGreenVoltage/current output positive
WhiteVoltage/current output negative


Selection Guide

Code and description



Remarks

LFG201

Wall Mounted CO2 monitor



Model


1

2000ppm



Measure Range

2

5000ppm



3

10000ppm




IV0

4~20mA&0~5V



Output

IV1

4~20mA&0~10V



RS

RS485/Modbus




A

Side Outlet
Cable Outlet
BRear Outlet

T
Terminal outletOutlet Form
DDirect outlet

LFG201

2

IV1

AT

Example of Selection

Note:

➀The terminal outlet is the welding terminal on the internal circuit board, without wire factory;

➁The direct outlet is the wire welded on the internal circuit board, the default 60cm outlet (other lengths of wires can becustomized).

Features of Wall Mounted CO2 monitor transmitter LFG201 (Upgraded Ver.)

  • Imported infrared light source and dual-channel thermopile detector

  • The sensor is oxygen-free and has a service life of more than 5 years

  • Long-term stability and reliability

  • Double-layer waterproof membrane design effectively prevents water vapor from entering

Applications of Wall Mounted CO2 monitor transmitter LFG201 (Upgraded Ver.)

The CO2 Transmitter Shows the carbon dioxide (CO2) concentration in the ambient air as a measure for air quality. A common application is for the HVAC system and construction industries. It is suitable for carbon dioxide gas measurement in indoor air quality detection, air conditioners, air purifiers, vegetable greenhouses and other occasions.

Product Inquiry