LEFOO Indoor Temperature and Humidity Transmitter LFH20 | |
Relative Humidity | |
Sensor | Digital type |
Range | 0%~100%RH |
Output | RS485/Modbus,0~10VDC, 4~20mA optional |
Accuracy | ±3%@ 20℃ & 20~80%RH |
Response time | ≤10s(25℃, slow flow air) |
Temperature | |
Sensor | Digital or RTD, refer to selection table |
Range | 0~50℃, -20~60℃, etc |
Output Signal | 4~20mA,0~10VDC, RS485/Modbus optional |
RTD(thermal resistor) | Refer to the selection table and RTD indexing table |
Accuracy | Digital sensor: ±0.3℃@20℃ ; RTD: Typical ±0.2~0.4℃@25℃, refer to selection table |
Power Supply | Voltage type/485 type 15~35VDC/24VAC±20% ; Current type 19.5~35VDC (RL=500Ω)/9.5~35VDC (RL=0Ω) |
Output Load | ≤500Ω(current type), ≥2KΩ(voltage type) |
Display | Optional LCD display with unit display and backlight (4~20mA without backlight) |
Shell Material | PC |
Working Environment | -20~60℃, 5%-95%RH(non-condensing) |
Protection Class | IP30 |
Code and Description | Remark | |||||||
LFH20 | Indoor Temperature Humidity Sensor | Model | ||||||
3 | ±3%RH(±0.3℃) | Accuracy | ||||||
A4 | 4~20mA(Two-wired) | Humidity output | ||||||
V10 | 0~10VDC(Three-wired) | |||||||
RS | RS485/Modbus | |||||||
N | No output | |||||||
A4 | 4~20mA(Two-wired) | Temperature output | ||||||
V10 | 0~10VDC(Three-wired) | |||||||
RS | RS485/Modbus | |||||||
0 | PT1000,±0.2℃@0℃ | |||||||
1 | PT100,±0.2℃@0℃ | |||||||
2 | NTC20K,±0.4℃@25℃ | |||||||
3 | NTC10K,±0.4℃@25℃ | |||||||
N | No output | |||||||
0 | Non | Range | ||||||
1 | 0~50℃ | |||||||
2 | -20~60 | |||||||
8 | Customizable | |||||||
0 | Without displa | Display | ||||||
1 | LCD digital display | |||||||
LFH20 | 3 | A4 | A4 | 1 | 1 | Selection example |