Air Differential Pressure Transducer | ||||
Note: Better accuracy performance than ±1%F.S is optional | ||||
![]() | ||||
General | Value | |||
Pressure Range | 0~±100Pa, 0~±1,000Pa, 0~±10,000Pa | |||
Overpressure capacity | 5KPa, 10KPa, 80KPa | |||
Accuracy | ±1%F.S | |||
Operating temperature | -20℃~70℃ | |||
Response time | 0.5s/1s/2s/4s | |||
Cable Connector | Cable maximum diameter Ø8mm | |||
Stability | Typical value:0.1%F.S Maximum value:0.2%F.S | |||
Protection Level | IP54 | |||
Electrical connections | Three-wired | Four-wired | Five-wired | |
Output signal | 4~20mA | 0~5VDC/ 0~10VDC | RS-485 | RS485+ 0~10VDC |
Power supply | 10~30 VDC | 16~30 VDC | 10~30VDC | 16~30 VDC |
Power consumption | ≤1.5W | |||
Pressure interface | Metal barbed interface,φ6.2mm | |||
Communication | RS-485 Standard interface, Modbus RTU protocol | |||
Certification | ROHS certification,CE certification | |||
Electromagnetic compatibility | Electromagnetic radiation:EN50081-1/-2;Electromagnetic sensitivity:EN50082-2 | |||
Lightning protection | Air conduction withstand voltage 8000V, shell and cable conduction withstand voltage 4000V |
Selection instructions | ||||||
Note: This Model has the ideal price-performance rate | ||||||
![]() | ||||||
Code and description | Remark | |||||
LFM108 | Low Differential Pressure Transducer | Model | ||||
101D | 101D=0±100Pa | 101G | 101G=0-100Pa | Measuring range G means one-way D means two-way | ||
102D | 102D=0±1000Pa | 102G | 102G=0-1000Pa | |||
251D | 251D=0±250Pa | 103G | 103G=0-10000Pa | |||
252D | 252D=0±2500Pa | 251G | 251G=0-250Pa | |||
051D | 051DD=0±50Pa | 252G | 252G=0-2500Pa | |||
501D | 501D=0±500Pa | 501G | 501G=0-500Pa | |||
502D | 502D=0±5000Pa | 502G | 502G=0-5000Pa | |||
103D | 103D=0±10000Pa | |||||
AL | 4~20mA | Output type | ||||
VL | 0~10V | |||||
VZ | 0~5V | |||||
MOD | RS485 | |||||
MVL | RS485、0~10VDC | |||||
MVZ | RS485、0~5VDC | |||||
MAL | RS485、4~20mA | |||||
LFM108 | 102G | VZ | Selection example |